山东大学学报(工学版)
山東大學學報(工學版)
산동대학학보(공학판)
JOURNAL OF SHANDONG UNIVERSITY(ENGINEERING SCIENCE)
2014年
5期
83-87
,共5页
冀翠莲%韩吉田%尹静%陈常念%任立波%孔令健
冀翠蓮%韓吉田%尹靜%陳常唸%任立波%孔令健
기취련%한길전%윤정%진상념%임립파%공령건
流动沸腾%传热系数关联式%传热%两相流%螺旋管
流動沸騰%傳熱繫數關聯式%傳熱%兩相流%螺鏇管
류동비등%전열계수관련식%전열%량상류%라선관
flow boiling%heat transfer coefficient correlation%heat transfer%two-phase flow%helically coiled tube
为了发展适于螺旋管内流动沸腾传热系数关联式,基于流动沸腾传热机理,引入参数Dn 数来修正复杂管道对传热系数的影响,并经过回归计算确定Dn 数的指数,从而发展了螺旋管内流动沸腾传热系数关联式。进一步分析了传热系数预测值与实验值的偏差随流量、干度的变化情况。利用以R134a为介质的螺旋管传热实验数据验证了该关联式的适用性,并采用平均相对误差(the mean relative error,MRE)和均方根误差(the root mean square error,RMSE)来衡量预测结果的准确性,计算出MRE在8.23%范围内,RMSE为0.532。该平均相对误差值和均方根误差值都比较小,表明回归计算结果符合要求。因此,复杂管道引入参数Dn 数建立传热系数关联式是非常适用的,并值得推广应用。
為瞭髮展適于螺鏇管內流動沸騰傳熱繫數關聯式,基于流動沸騰傳熱機理,引入參數Dn 數來脩正複雜管道對傳熱繫數的影響,併經過迴歸計算確定Dn 數的指數,從而髮展瞭螺鏇管內流動沸騰傳熱繫數關聯式。進一步分析瞭傳熱繫數預測值與實驗值的偏差隨流量、榦度的變化情況。利用以R134a為介質的螺鏇管傳熱實驗數據驗證瞭該關聯式的適用性,併採用平均相對誤差(the mean relative error,MRE)和均方根誤差(the root mean square error,RMSE)來衡量預測結果的準確性,計算齣MRE在8.23%範圍內,RMSE為0.532。該平均相對誤差值和均方根誤差值都比較小,錶明迴歸計算結果符閤要求。因此,複雜管道引入參數Dn 數建立傳熱繫數關聯式是非常適用的,併值得推廣應用。
위료발전괄우라선관내류동비등전열계수관련식,기우류동비등전열궤리,인입삼수Dn 수래수정복잡관도대전열계수적영향,병경과회귀계산학정Dn 수적지수,종이발전료라선관내류동비등전열계수관련식。진일보분석료전열계수예측치여실험치적편차수류량、간도적변화정황。이용이R134a위개질적라선관전열실험수거험증료해관련식적괄용성,병채용평균상대오차(the mean relative error,MRE)화균방근오차(the root mean square error,RMSE)래형량예측결과적준학성,계산출MRE재8.23%범위내,RMSE위0.532。해평균상대오차치화균방근오차치도비교소,표명회귀계산결과부합요구。인차,복잡관도인입삼수Dn 수건립전열계수관련식시비상괄용적,병치득추엄응용。
In order to develop flow boiling heat transfer coefficient correlations for helically coiled tube,based on the mechanism of flow boiling heat transfer.The Dn factor was introduced to consider complex pipeline effects on flow boil-ing heat transfer.The index of the Dn factor was gained by using the regression method.And relation of the ratio of the experimental and predicted values with the mass flow rate and vapor quality was further analyzed.A new heat transfer coefficient correlation of flow boiling in helically coiled tube was developed.The applicability for the heat transfer coef-ficient correlation was validated by experimental data of flow boiling heat transfer in helically coiled tube with R134a. The MRE and the RMSE were used to measure the accuracy of regression results,with MRE and RMSE being 8.23%and 0.532,respectively.The MRE and the RMSE were small,the regression results conformed to the requirements. Therefore,the method is very applicable,and is worthy of popularization.