工业厂房%地表水地源热泵%全寿命周期成本(LCC)%负荷%冷水泵%变频控制
工業廠房%地錶水地源熱泵%全壽命週期成本(LCC)%負荷%冷水泵%變頻控製
공업엄방%지표수지원열빙%전수명주기성본(LCC)%부하%랭수빙%변빈공제
industrial plant%surface water source heat pump%life-cycle cost (LCC)%load%chilled water pump%frequency conversion control
建立了全寿命周期成本(LCC)数学模型,计算分析了该工业厂房分别采用地表水地源热泵系统与常规冷热源系统的LCC 值。分析了能耗的组成及特征,地表水地源热泵系统中热泵机组及冷水泵的能耗费用占运行成本的比例较大,分别为76.2%和12.9%。基于 LCC分析了不同负荷率下多台机组并联运行时负荷承担方式不同对机组COP 的影响,结果显示,在冷水供回水温差、源水侧供回水温差一定的情况下,部分负荷率小于28%时2台机组均匀分担负荷,大于28%时4台机组均匀分担负荷,系统 LCC 值最小,为2857.5万元。同时当冷水泵采用变频控制时,系统的LCC 值更小,为2825.9万元。
建立瞭全壽命週期成本(LCC)數學模型,計算分析瞭該工業廠房分彆採用地錶水地源熱泵繫統與常規冷熱源繫統的LCC 值。分析瞭能耗的組成及特徵,地錶水地源熱泵繫統中熱泵機組及冷水泵的能耗費用佔運行成本的比例較大,分彆為76.2%和12.9%。基于 LCC分析瞭不同負荷率下多檯機組併聯運行時負荷承擔方式不同對機組COP 的影響,結果顯示,在冷水供迴水溫差、源水側供迴水溫差一定的情況下,部分負荷率小于28%時2檯機組均勻分擔負荷,大于28%時4檯機組均勻分擔負荷,繫統 LCC 值最小,為2857.5萬元。同時噹冷水泵採用變頻控製時,繫統的LCC 值更小,為2825.9萬元。
건립료전수명주기성본(LCC)수학모형,계산분석료해공업엄방분별채용지표수지원열빙계통여상규랭열원계통적LCC 치。분석료능모적조성급특정,지표수지원열빙계통중열빙궤조급랭수빙적능모비용점운행성본적비례교대,분별위76.2%화12.9%。기우 LCC분석료불동부하솔하다태궤조병련운행시부하승담방식불동대궤조COP 적영향,결과현시,재랭수공회수온차、원수측공회수온차일정적정황하,부분부하솔소우28%시2태궤조균균분담부하,대우28%시4태궤조균균분담부하,계통 LCC 치최소,위2857.5만원。동시당랭수빙채용변빈공제시,계통적LCC 치경소,위2825.9만원。
Establishes a mathematical model of life-cycle cost (LCC),calculates and analyses LCC values of both surface water source heat pump system and conventional heating and cooling systems in the industrial plant. Analyses the composition and characteristics of energy consumption.The results show that the heat pump unit and chilled water pump consume a larger proportion of energy,which are 76.2% and 12.9% of energy consumption of the whole surface water source heat pump system respectively.Based on LCC,analyses the influence of load share mode of multiple parallel units on COP of units in different load rates.The results show that on the condition of the steady temperature differences between supply and return water for both chilled water and the water source,two units share the load evenly when the part-load rate is less than 28%,and four units share the load evenly when the part-load rate is greater than 28%,then the system LCC reaches its minimum value at 28.575 million yuan.Meanwhile,the system LCC reaches even smaller value at 28.259 million yuan when the chilled water pump is under frequency conversion control.