针对与发电厂、运行变电站接地网相连的架空避雷线、电力电缆外护套分流电流导致的接地网接地阻抗测量误差问题,提出了利用杆塔分流测量技术精确测量接地网阻抗的方法,即向接地网注入异频测试电流,由在测量点的测量设备主机实时采样、记录测试电流幅值和相角,将测试电流波形信号在测量区域无线发射。同时,在变电站出线各构架基脚处接收该信号,用柔性罗氏线圈测量各构架基脚所流过的异频电流的模值和相角,进而确定分流电流值并计算分流电流和,在测试电流中去除该分流电流和,准确计算出接地网的实际电流值及接地网接地阻抗值。该方法可提高大型接地网接地特性参数测试的准确性。
針對與髮電廠、運行變電站接地網相連的架空避雷線、電力電纜外護套分流電流導緻的接地網接地阻抗測量誤差問題,提齣瞭利用桿塔分流測量技術精確測量接地網阻抗的方法,即嚮接地網註入異頻測試電流,由在測量點的測量設備主機實時採樣、記錄測試電流幅值和相角,將測試電流波形信號在測量區域無線髮射。同時,在變電站齣線各構架基腳處接收該信號,用柔性囉氏線圈測量各構架基腳所流過的異頻電流的模值和相角,進而確定分流電流值併計算分流電流和,在測試電流中去除該分流電流和,準確計算齣接地網的實際電流值及接地網接地阻抗值。該方法可提高大型接地網接地特性參數測試的準確性。
침대여발전엄、운행변전참접지망상련적가공피뢰선、전력전람외호투분류전류도치적접지망접지조항측량오차문제,제출료이용간탑분류측량기술정학측량접지망조항적방법,즉향접지망주입이빈측시전류,유재측량점적측량설비주궤실시채양、기록측시전류폭치화상각,장측시전류파형신호재측량구역무선발사。동시,재변전참출선각구가기각처접수해신호,용유성라씨선권측량각구가기각소류과적이빈전류적모치화상각,진이학정분류전류치병계산분류전류화,재측시전류중거제해분류전류화,준학계산출접지망적실제전류치급접지망접지조항치。해방법가제고대형접지망접지특성삼수측시적준학성。
Aimed at the problem that the ground impedance measuring existed deviation due to the shunt current of overhead ground wires and power cables' outer sheath connected with the power plants or substations, proposed a measuring method based on wireless transmission principle. Firstly, the amplitude and phase of the different-frequency test current were recorded at the measuring point in real time as a reference waveform signal, and the current waveform was transmitted to the field outlet structure wirelessly. These signals were collected at the structure foots, from where the phase difference of current was measured using flexible Rogowski coils. Then, the shunt vector was subtracted from the tested current vector to acquire actual injecting current through grounding network, in which way could improve the test accuracy of large grounding characteristic parameters.