介绍一起由闸刀辅助接点损坏引起母线保护CT断线告警的故障,通过对BP-2B差流回路和闸刀开入逻辑的分析,得出此故障是由于外部回路的闸刀接点开入错误所导致,提出多种可行性解决方案,以期减少和杜绝因闸刀辅助接点损坏或接触不良可能引起的危害。
介紹一起由閘刀輔助接點損壞引起母線保護CT斷線告警的故障,通過對BP-2B差流迴路和閘刀開入邏輯的分析,得齣此故障是由于外部迴路的閘刀接點開入錯誤所導緻,提齣多種可行性解決方案,以期減少和杜絕因閘刀輔助接點損壞或接觸不良可能引起的危害。
개소일기유갑도보조접점손배인기모선보호CT단선고경적고장,통과대BP-2B차류회로화갑도개입라집적분석,득출차고장시유우외부회로적갑도접점개입착오소도치,제출다충가행성해결방안,이기감소화두절인갑도보조접점손배혹접촉불량가능인기적위해。
Introduction was made to the malfunction of current transformer disconnection alarm owing to the auxiliary contact broken in isolating switch. This paper analyzed the BP-2B difference stream circuit and the making and breaking logic in isolating switch. The mistakes caused by making and breaking of the contacts in isolating switch of peripheral circuit made bus protection out of services. Some feasibility solutions were proposed, so as to reduce and avoid the negative infiuence of the auxiliary contact broken and poor con-tact in isolating switch.