在输配电系统中,合理配置无功补偿装置是提高电压质量、增强系统稳定性、节能降耗和提高有功功率输送能力的重要措施。无功补偿装置运行状况的好坏,直接影响着电力系统的供电质量、安全稳定运行。但由于并联电容器无功补偿装置基本为固定式补偿,在负荷变化较大的地区,经常会出现过补偿的现象和过电压的问题,而动态无功补偿装置造价大,维护难度大。在地区电网的适用性不强。同时,并联电容器装置所用的干式空芯串联电抗器,其发生的故障中70%为匝间短路故障所引起,出现匝间短路后,后果往往是电抗器起火烧毁。本文依据芜湖供电公司近几年并联电容器装置的故障为参考,为解决上述问题,研制了一套无功分组自动控制补偿兼电抗器匝间短路保护装置。
在輸配電繫統中,閤理配置無功補償裝置是提高電壓質量、增彊繫統穩定性、節能降耗和提高有功功率輸送能力的重要措施。無功補償裝置運行狀況的好壞,直接影響著電力繫統的供電質量、安全穩定運行。但由于併聯電容器無功補償裝置基本為固定式補償,在負荷變化較大的地區,經常會齣現過補償的現象和過電壓的問題,而動態無功補償裝置造價大,維護難度大。在地區電網的適用性不彊。同時,併聯電容器裝置所用的榦式空芯串聯電抗器,其髮生的故障中70%為匝間短路故障所引起,齣現匝間短路後,後果往往是電抗器起火燒燬。本文依據蕪湖供電公司近幾年併聯電容器裝置的故障為參攷,為解決上述問題,研製瞭一套無功分組自動控製補償兼電抗器匝間短路保護裝置。
재수배전계통중,합리배치무공보상장치시제고전압질량、증강계통은정성、절능강모화제고유공공솔수송능력적중요조시。무공보상장치운행상황적호배,직접영향착전력계통적공전질량、안전은정운행。단유우병련전용기무공보상장치기본위고정식보상,재부하변화교대적지구,경상회출현과보상적현상화과전압적문제,이동태무공보상장치조개대,유호난도대。재지구전망적괄용성불강。동시,병련전용기장치소용적간식공심천련전항기,기발생적고장중70%위잡간단로고장소인기,출현잡간단로후,후과왕왕시전항기기화소훼。본문의거무호공전공사근궤년병련전용기장치적고장위삼고,위해결상술문제,연제료일투무공분조자동공제보상겸전항기잡간단로보호장치。
Reasonably allocating reactive power compensation units in the power transmission and distribution system is an important measure to improve the voltage quality,to strengthen the system stability,to save energy and to improve the active power delivery capacity.The running state of reactive power compensation units influences the power supply quality and safe and stable operation of the electric power system directly.However,as most reactive power compensation units of parallel capacitor mainly adopt the fixed compensation,it is very likely to appear over-compensation and over-voltage in regions with larger load change.The dynamic reactive power compensation units are expensive and hard-to-maintain.Therefore,the applicability in regional power grid is weak.In addition,the 70%of faults in the dry-type air series reactor used in parallel capacitors are caused by the inter-turn short circuit fault,which always have the electric reactor burnt.This paper takes the parallel capacitors used by Wuhu Power Supply Company in the past years as reference and researches a set of equipment with functions of automatic control of reactive power grouping and inter-turn short circuit fault protection.