发电机出口开关%操作结构%解体大修
髮電機齣口開關%操作結構%解體大脩
발전궤출구개관%조작결구%해체대수
switch of generator output end%operation device%overhaul
介绍了水布垭电厂发电机出口开关操作机构故障情况及其解体大修主要工艺流程、工艺方法。解体检查后,对03开关操作机构的故障进行了分析,认为密封圈老化是造成操作机构随机性频繁打压的最主要原因,并提出了防范措施。
介紹瞭水佈埡電廠髮電機齣口開關操作機構故障情況及其解體大脩主要工藝流程、工藝方法。解體檢查後,對03開關操作機構的故障進行瞭分析,認為密封圈老化是造成操作機構隨機性頻繁打壓的最主要原因,併提齣瞭防範措施。
개소료수포오전엄발전궤출구개관조작궤구고장정황급기해체대수주요공예류정、공예방법。해체검사후,대03개관조작궤구적고장진행료분석,인위밀봉권노화시조성조작궤구수궤성빈번타압적최주요원인,병제출료방범조시。
The overhauling of No .3 switch operation device of generator output end in Shuibuya hydropower station is in-troduced , including the fault condition , main process and technical procedures of the overhaul .Possible reason of this fault is also analyzed after the overhauling .It shows that aging of the seal could be the main reason of the frequent ran-dom faulty operation of the switch device .Precautions are then proposed .