中国电机工程学报
中國電機工程學報
중국전궤공정학보
ZHONGGUO DIANJI GONGCHENG XUEBAO
2014年
33期
5948-5955
,共8页
陈维江%傅中%王贻平%孙岗%叶剑涛%刘楠%陈国强%夏令志
陳維江%傅中%王貽平%孫崗%葉劍濤%劉楠%陳國彊%夏令誌
진유강%부중%왕이평%손강%협검도%류남%진국강%하령지
1 000 kV交流%同塔双回线路%相参数%测量
1 000 kV交流%同塔雙迴線路%相參數%測量
1 000 kV교류%동탑쌍회선로%상삼수%측량
1000kV AC%double-circuit transmission lines on the same tower%phase parameters%measurement
输电线路工频相参数是线路过电压计算的基本参数,获取1000 kV交流同塔双回线路的相参数对于指导工程运行是必要的。短距离输电线路相参数测量可不考虑分布参数特性也能获得较准确的结果,对于长距离线路会产生一定的误差。为获取长距离特高压线路准确的相参数,利用π型和分布参数等值电路对多导线系统进行建模分析,提出了测量各相导线首末端电压、电流列出方程组求解相间互电容的方法。基于线路分布参数特性推导出相间互阻抗计算公式,采用求解长线方程的方法获得了相、自参数。仿真结果表明,该文方法可减小误差。通过实测计算获得了皖电东送淮南至上海1000 kV交流同塔双回线路淮芜Ⅰ线与Ⅱ线的相参数,为工程中过电压计算等应用提供了准确的参数。
輸電線路工頻相參數是線路過電壓計算的基本參數,穫取1000 kV交流同塔雙迴線路的相參數對于指導工程運行是必要的。短距離輸電線路相參數測量可不攷慮分佈參數特性也能穫得較準確的結果,對于長距離線路會產生一定的誤差。為穫取長距離特高壓線路準確的相參數,利用π型和分佈參數等值電路對多導線繫統進行建模分析,提齣瞭測量各相導線首末耑電壓、電流列齣方程組求解相間互電容的方法。基于線路分佈參數特性推導齣相間互阻抗計算公式,採用求解長線方程的方法穫得瞭相、自參數。倣真結果錶明,該文方法可減小誤差。通過實測計算穫得瞭皖電東送淮南至上海1000 kV交流同塔雙迴線路淮蕪Ⅰ線與Ⅱ線的相參數,為工程中過電壓計算等應用提供瞭準確的參數。
수전선로공빈상삼수시선로과전압계산적기본삼수,획취1000 kV교류동탑쌍회선로적상삼수대우지도공정운행시필요적。단거리수전선로상삼수측량가불고필분포삼수특성야능획득교준학적결과,대우장거리선로회산생일정적오차。위획취장거리특고압선로준학적상삼수,이용π형화분포삼수등치전로대다도선계통진행건모분석,제출료측량각상도선수말단전압、전류렬출방정조구해상간호전용적방법。기우선로분포삼수특성추도출상간호조항계산공식,채용구해장선방정적방법획득료상、자삼수。방진결과표명,해문방법가감소오차。통과실측계산획득료환전동송회남지상해1000 kV교류동탑쌍회선로회무Ⅰ선여Ⅱ선적상삼수,위공정중과전압계산등응용제공료준학적삼수。
ABSTRACT:Power frequency phase parameters of transmission lines are essential parameters of overvoltage calculation, so it is necessary to obtain the phase parameters of 1000kV AC double-circuit transmission lines on the same tower before the lines are put into operation. Phase parameters of short distance lines can be accurately obtained by measurement and calcalation without taking into consideration their distributed parameter characteristic, while errors tend to arisefor long distance lines. In order to get accurate phase parameters of long distance UHV transmission lines, a multiconductor transmission line was modeled and analyzed byπ lumped parameter and distributed parameter equivalent circuit respectively in this paper. A method was proposed to obtain mutual capacitances between phase conductors by measuring the voltages or currents at both ends of each phase conductor and calculating mutual admittances equations between phase conductors. Equations of mutual impedances between conductors were deduced based on the distributed parameter characteristic of lines. Self-parameters of phase conductors were calculated according to the relationship equations between the voltages and currents on both sides of phase conductors. The results indicate that calculation errors of the parameters can be reduced by adopting the methods, which has been verified by means of simulation. The methods were used to obtain the phase parameters of 1000 kV Huainan-WuhuⅠandⅡ lines of eastward transmission of Anhui electric power and can provide exact data for overvoltage calculation of the project.