输电线路的可听噪声是发展特高压直流输电需要解决的关键技术问题之一.特高压直流试验线段和电晕笼是研究实际线路可听噪声的重要试验设施.研究特高压直流长、短输电线路可听噪声的转换关系,对于利用特高压直流试验基地建设的试验线段和电晕笼的试验结果预测实际特高压输电线路的可听噪声有重要意义.推导了由可听噪声产生功率表示的任意长度输电线路下方地面各位置处可听噪声的计算公式,并由此得出直流长、短输电线路可听噪声之间的关联关系.当单回直流试验线段的长度大于测量点到正极导线距离的10倍、测量点在线路纵向上偏移中心点不超过线路总长的20%时,可近似认为试验线段下可听噪声的测量结果为实际无限长线路相同位置处的可听噪声水平.
輸電線路的可聽譟聲是髮展特高壓直流輸電需要解決的關鍵技術問題之一.特高壓直流試驗線段和電暈籠是研究實際線路可聽譟聲的重要試驗設施.研究特高壓直流長、短輸電線路可聽譟聲的轉換關繫,對于利用特高壓直流試驗基地建設的試驗線段和電暈籠的試驗結果預測實際特高壓輸電線路的可聽譟聲有重要意義.推導瞭由可聽譟聲產生功率錶示的任意長度輸電線路下方地麵各位置處可聽譟聲的計算公式,併由此得齣直流長、短輸電線路可聽譟聲之間的關聯關繫.噹單迴直流試驗線段的長度大于測量點到正極導線距離的10倍、測量點在線路縱嚮上偏移中心點不超過線路總長的20%時,可近似認為試驗線段下可聽譟聲的測量結果為實際無限長線路相同位置處的可聽譟聲水平.
수전선로적가은조성시발전특고압직류수전수요해결적관건기술문제지일.특고압직류시험선단화전훈롱시연구실제선로가은조성적중요시험설시.연구특고압직류장、단수전선로가은조성적전환관계,대우이용특고압직류시험기지건설적시험선단화전훈롱적시험결과예측실제특고압수전선로적가은조성유중요의의.추도료유가은조성산생공솔표시적임의장도수전선로하방지면각위치처가은조성적계산공식,병유차득출직류장、단수전선로가은조성지간적관련관계.당단회직류시험선단적장도대우측량점도정겁도선거리적10배、측량점재선로종향상편이중심점불초과선로총장적20%시,가근사인위시험선단하가은조성적측량결과위실제무한장선로상동위치처적가은조성수평.
Audible noise (AN) of transmission lines is one of the key technical problems to be solved for the development of UHVDC power transmission. The UHVDC test line and corona cage are important experimental facilities for the research on AN of actual transmission lines. It is crucial to research the AN transformation relation between long and short UHVDC transmission lines for predicting the AN level of actual UHV transmission line by experimental results of test line constructed in UHVDC test base. The calculation formula for AN level at different positions beneath transmission line with arbitrary length, which is expressed by the acoustic power of the corona sources, is derived and it follows that the incidence relation between AN level of long UHVDC transmission line and that of short transmission line is attained. Under the measurement conditions that the length of single-circuit UHVDC test line is larger than 10 times of the distance from the measuring point to positive polar conductor and the offset of measuring point in longitudinal direction of transmission line is not larger than 20% of total length of the test line, the measured AN level beneath the test line can be approximately regarded as the AN level at the same position of actual infinite long lines.