500kV某变电站运行人员运行监视中发现500kV线路后台电压指示为Uab529.26kV、Ubc525.94kV、Uca525.96kV,Uab电压明显偏高。随即对线路PT二次进行单相测量,发现A相二次电压高于其它两相0.84V。
500kV某變電站運行人員運行鑑視中髮現500kV線路後檯電壓指示為Uab529.26kV、Ubc525.94kV、Uca525.96kV,Uab電壓明顯偏高。隨即對線路PT二次進行單相測量,髮現A相二次電壓高于其它兩相0.84V。
500kV모변전참운행인원운행감시중발현500kV선로후태전압지시위Uab529.26kV、Ubc525.94kV、Uca525.96kV,Uab전압명현편고。수즉대선로PT이차진행단상측량,발현A상이차전압고우기타량상0.84V。
The operating personnel of one 500kV transformer substation found that background voltage instructions of 500kV line was Uab529.26kV, Ubc525.94kV, Uca525.96kV, which showed that the Uab voltage was significantly higher. Then the secondary single-phase measurement of line PT was done and it found that the A-phase secondary voltage was higher than the other two phases 0.84V.