电网技术
電網技術
전망기술
POWER SYSTEM TECHNOLOGY
2015年
1期
76-82
,共7页
刘羽超%郭春义%许韦华%赵成勇%阳岳希%李春华
劉羽超%郭春義%許韋華%趙成勇%暘嶽希%李春華
류우초%곽춘의%허위화%조성용%양악희%리춘화
高压直流输电%换相失败%功率分量检测%电流指令速动
高壓直流輸電%換相失敗%功率分量檢測%電流指令速動
고압직류수전%환상실패%공솔분량검측%전류지령속동
HVDC%commutation failure%power component detection%quick current order limiter
为减小直流输电系统发生换相失败的概率,分析了换相失败机理,得出促进换相过程的关键。首先,基于数字信号处理器实时监测装置,结合故障电压和故障电流特征,提出了一种功率分量检测法。然后,利用该方法的故障检测结果,提出了一种基于电流指令速动的控制方法,能迅速减小直流电流。理论分析表明,功率分量检测法具有更好的灵敏性与准确性,而电流指令速动控制不仅能快速减小换相面积,而且在一定程度上增大了换相电压。在PSCAD/EMTDC中搭建了双馈入直流输电系统模型。仿真结果与理论分析相符,证明所提出的功率分量检测法与电流指令速动控制具有一定的优越性,能降低换相失败发生概率,减小换相失败的影响范围。
為減小直流輸電繫統髮生換相失敗的概率,分析瞭換相失敗機理,得齣促進換相過程的關鍵。首先,基于數字信號處理器實時鑑測裝置,結閤故障電壓和故障電流特徵,提齣瞭一種功率分量檢測法。然後,利用該方法的故障檢測結果,提齣瞭一種基于電流指令速動的控製方法,能迅速減小直流電流。理論分析錶明,功率分量檢測法具有更好的靈敏性與準確性,而電流指令速動控製不僅能快速減小換相麵積,而且在一定程度上增大瞭換相電壓。在PSCAD/EMTDC中搭建瞭雙饋入直流輸電繫統模型。倣真結果與理論分析相符,證明所提齣的功率分量檢測法與電流指令速動控製具有一定的優越性,能降低換相失敗髮生概率,減小換相失敗的影響範圍。
위감소직류수전계통발생환상실패적개솔,분석료환상실패궤리,득출촉진환상과정적관건。수선,기우수자신호처리기실시감측장치,결합고장전압화고장전류특정,제출료일충공솔분량검측법。연후,이용해방법적고장검측결과,제출료일충기우전류지령속동적공제방법,능신속감소직류전류。이론분석표명,공솔분량검측법구유경호적령민성여준학성,이전류지령속동공제불부능쾌속감소환상면적,이차재일정정도상증대료환상전압。재PSCAD/EMTDC중탑건료쌍궤입직류수전계통모형。방진결과여이론분석상부,증명소제출적공솔분량검측법여전류지령속동공제구유일정적우월성,능강저환상실패발생개솔,감소환상실패적영향범위。
ABSTRACT:To reduce the probability of commutation failure in HVDC power transmission system, the mechanism of commutation failure is analyzed and the key factors to promote the commutation process are obtained. Firstly, based on real-time monitoring device composed of digital signal processor and combining with the features of fault voltage and fault current, a power component detection method is proposed; secondly, based on the fault detection results a quick current order limiter based control method, which can quickly reduce the DC current, is put forward. Theoretical analysis shows that the proposed power component detection method possesses better sensitivity and accuracy, and the quick current order limiter based control can reduce the commutation area while increasing the commutation voltage. A model of dual-infeed HVDC power transmission system is constructed in the environment of PSCAD/EMTDC, and the simulation results conform to the results of theoretical analysis, thus it is proved that the proposed power component detection method and quick current order limiter based control possess a certain superiority, and using them the probability of occurring commutation failure and be reduced and the impacting range of commutation failure can be narrowed down.