针对某电厂1、2、3号锅炉选择性催化还原法(selective catalytic reduction,SCR)脱硝系统现场调试过程中遇到的技术难题,进行了研究并得到工程应用。分析了稀释风机联锁保护、氨–空气混合器关断阀的联锁保护、供氨调节阀自动控制等方面存在的技术难题,并提出相应的解决方法。主要结论如下:氨–空气混合器前关断阀应加入到联锁保护逻辑中;为防止当供氨压力低时,如果供氨管道上逆止阀工作不正常则可能存在稀释风向供氨管道内倒灌空气而引起不安全因素,在氨–空气混合器关断阀的联锁保护关闭条件中添加此项逻辑联锁保护条件;脱硝系统自动控制以跟踪出口NOx 含量为依据,建议运行人员在脱硝系统满足环保投运要求的条件下,尽量根据入口NOx 含量变化情况及时调整系统脱硝率,减少出现脱硝率过高的情况。
針對某電廠1、2、3號鍋爐選擇性催化還原法(selective catalytic reduction,SCR)脫硝繫統現場調試過程中遇到的技術難題,進行瞭研究併得到工程應用。分析瞭稀釋風機聯鎖保護、氨–空氣混閤器關斷閥的聯鎖保護、供氨調節閥自動控製等方麵存在的技術難題,併提齣相應的解決方法。主要結論如下:氨–空氣混閤器前關斷閥應加入到聯鎖保護邏輯中;為防止噹供氨壓力低時,如果供氨管道上逆止閥工作不正常則可能存在稀釋風嚮供氨管道內倒灌空氣而引起不安全因素,在氨–空氣混閤器關斷閥的聯鎖保護關閉條件中添加此項邏輯聯鎖保護條件;脫硝繫統自動控製以跟蹤齣口NOx 含量為依據,建議運行人員在脫硝繫統滿足環保投運要求的條件下,儘量根據入口NOx 含量變化情況及時調整繫統脫硝率,減少齣現脫硝率過高的情況。
침대모전엄1、2、3호과로선택성최화환원법(selective catalytic reduction,SCR)탈초계통현장조시과정중우도적기술난제,진행료연구병득도공정응용。분석료희석풍궤련쇄보호、안–공기혼합기관단벌적련쇄보호、공안조절벌자동공제등방면존재적기술난제,병제출상응적해결방법。주요결론여하:안–공기혼합기전관단벌응가입도련쇄보호라집중;위방지당공안압력저시,여과공안관도상역지벌공작불정상칙가능존재희석풍향공안관도내도관공기이인기불안전인소,재안–공기혼합기관단벌적련쇄보호관폐조건중첨가차항라집련쇄보호조건;탈초계통자동공제이근종출구NOx 함량위의거,건의운행인원재탈초계통만족배보투운요구적조건하,진량근거입구NOx 함량변화정황급시조정계통탈초솔,감소출현탈초솔과고적정황。
Aiming at technical difficulties in field commissioning process of selective catalytic reduction denitration system of No.1 ,No.2 and No.3 boilers in some power plant,research and engineering application was conducted. Technical difficul-ties in dilution fan interlock protection, interlock protection of shut-off valve of ammonia-air commingler and automatic control of ammonia supply adjusting valve were analyzed and relevant solutions were proposed. Main conclusions were as fol-lows:front shut-off valve of ammonia-air commingler should be added in interlock protection logic,for preventing unsafe factors caused for reason of air flow backward into the ammonia supply pipe by dilution wind resulted from abnormal action of upward check valve on ammonia supply pipe when ammonia supply pressure was low,this logic interlock protection con-dition was to be added in interlock protection shut-down conditions for shut-off valve of the ammonia-air commingler. On the basis of NOx content at the exit for automation control of denitration system,operation crews were suggested to adjust denitration ratio in time according to changes of NOx content at the entrance and reduce situation of higher denitration ratio under the condition of denitration system meeting requirement for environmental protection operation.