针对四川省绵阳市的水资源条件,提出用地源水代替7℃冷冻水通入表冷器对空气进行降温除湿处理,并进行了理论分析,结果表明冷水温度提高到16℃时,仍然具有良好的除湿效果。
針對四川省綿暘市的水資源條件,提齣用地源水代替7℃冷凍水通入錶冷器對空氣進行降溫除濕處理,併進行瞭理論分析,結果錶明冷水溫度提高到16℃時,仍然具有良好的除濕效果。
침대사천성면양시적수자원조건,제출용지원수대체7℃냉동수통입표랭기대공기진행강온제습처리,병진행료이론분석,결과표명랭수온도제고도16℃시,잉연구유량호적제습효과。
According to the water resource conditions in Mianyang of Sichuan Province,the paper points out the cooling and dehumidification role of the ground-source water taking the place of 7 ℃ cooled water into the surface air cooler,undertakes the theoretic analysis,and proves by the result that the better dehumidification effect can be achieved when the temperature of cool water is raised to 16 ℃.