针对变电站10 kV开关柜断路器、隔离开关触头接触部位及其他导电排连接部位在长期运行过程中因表面氧化腐蚀、紧固螺栓松动导致接触电阻增大而引起发热故障的问题,提出并研发了基于声表面波技术的适用于变电站10 kV开关柜关键点测温的无源无线式在线测温系统。该系统通过现有变电站综合数据网实现测温信息的统一采集与传输,具有远程智能分析和诊断、实时和历史数据报表统计、Web浏览发布和短信告警等功能,并已成功应用于中山供电局110 kV泰丰变电站、文安变电站、裕丰变电站,有效监测了10 kV开关柜设备实时发热情况,实现了各变电站测温数据的集中管理,为10 kV开关柜设备状态检修、及时消缺提供了可靠的数据支持。
針對變電站10 kV開關櫃斷路器、隔離開關觸頭接觸部位及其他導電排連接部位在長期運行過程中因錶麵氧化腐蝕、緊固螺栓鬆動導緻接觸電阻增大而引起髮熱故障的問題,提齣併研髮瞭基于聲錶麵波技術的適用于變電站10 kV開關櫃關鍵點測溫的無源無線式在線測溫繫統。該繫統通過現有變電站綜閤數據網實現測溫信息的統一採集與傳輸,具有遠程智能分析和診斷、實時和歷史數據報錶統計、Web瀏覽髮佈和短信告警等功能,併已成功應用于中山供電跼110 kV泰豐變電站、文安變電站、裕豐變電站,有效鑑測瞭10 kV開關櫃設備實時髮熱情況,實現瞭各變電站測溫數據的集中管理,為10 kV開關櫃設備狀態檢脩、及時消缺提供瞭可靠的數據支持。
침대변전참10 kV개관거단로기、격리개관촉두접촉부위급기타도전배련접부위재장기운행과정중인표면양화부식、긴고라전송동도치접촉전조증대이인기발열고장적문제,제출병연발료기우성표면파기술적괄용우변전참10 kV개관거관건점측온적무원무선식재선측온계통。해계통통과현유변전참종합수거망실현측온신식적통일채집여전수,구유원정지능분석화진단、실시화역사수거보표통계、Web류람발포화단신고경등공능,병이성공응용우중산공전국110 kV태봉변전참、문안변전참、유봉변전참,유효감측료10 kV개관거설비실시발열정황,실현료각변전참측온수거적집중관리,위10 kV개관거설비상태검수、급시소결제공료가고적수거지지。
In allusion to problems of heat faults of contact sites of breakers,disconnector contacts and other joint parts of conducting bars of 1 0 kV switch cabinet in substation caused by surface oxide corrosion and fastening bolts looseness that may result in contact resistance increase,a kind of passive wireless online temperature measurement system applicable to tempera-ture measurement on key points of 1 0 kV switch cabinet based on surface acoustic wave technology was proposed and devel-oped. By means of existing substation comprehensive data network,this system could realize unified acquisition and trans-mission of temperature measurement information and it was provided with functions such as remote intelligent analysis and diagnosis,real-time and historical data statistic,Web browse and publishing and message alarm. This system had been suc-cessfully applied in 1 1 0 kV Taifen substation,Wenan substation and Yufeng substation of Zhongshan power supply bureau which had effectively monitored real-time heating of 1 0 kV switch cabinet equipments,realized centralized management on temperature measurement data of each substation and provided reliable support for state overhaul and timely defects elimina-tion of 1 0 kV switch cabinet equipments.