电力系统自动化
電力繫統自動化
전력계통자동화
AUTOMATION OF ELECTRIC POWER SYSTEMS
2015年
3期
14-22
,共9页
fault ride-through%feed forward DC voltage control%offshore wind power%voltage source converter-high voltage direct current(VSC-HVDC)
To achieve active control of the AC voltage magnitude of wind power plant(WPP) collector network and improve the fault ride-through (FRT) capability,an FRT scheme based on feed forward DC voltage control is presented for voltage source converter-high voltage direct current(VSC-HVDC) connected offshore WPPs.During steady state operation,an open loop AC voltage control is implemented at the WPP-side VSC of the HVDC system so that any possible control interactions between WPP-side VSC and VSC of wind turbine are minimized.Whereas during any grid fault,a dynamic AC voltage reference is made according to both the DC voltage error and AC active current from the WPP collector system,thus ensuring fast and robust FRT of the VSC-HVDC-connected offshore WPPs.Under the unbalanced fault condition in the host power system,the resulting oscillatory DC voltage is directly used in the VSC AC voltage controller at the WPP side so that the WPP collector system voltage also reflects the unbalance in the main grid.Time domain simulations are performed to verify the efficacy of the FRT scheme based on the proposed feed forward DC voltage control.Simulation results show satisfactory FRT responses of the VSC-HVDC-connected offshore WPP under balanced and unbalanced faults in the host power system,as is shown under a serious fault in the WPP collector network.