对模块化多电平换流器(MMC)在正弦脉宽调制方式下子模块上下管开关器件的投入概率进行分析。结合上下管开关器件的投入概率,导出上下管开关器件等效电流的表达式。以子模块电容器在一个基频周期内的电压变化量是零为基础,推导出子模块电容器电压与电容器电容、负载功率因数、调制比及阀侧交流电流峰值之间的关系,并解析出上下管开关器件的平均电流与有效电流。利用开关器件制造厂商提供的损耗相关参数,对厦门柔性直流示范工程 MMC 在整流状态和逆变状态下的损耗和结温进行计算。计算结果表明,损耗计算和结温估算模型能为 MMC 冷却系统的配置提供参考。
對模塊化多電平換流器(MMC)在正絃脈寬調製方式下子模塊上下管開關器件的投入概率進行分析。結閤上下管開關器件的投入概率,導齣上下管開關器件等效電流的錶達式。以子模塊電容器在一箇基頻週期內的電壓變化量是零為基礎,推導齣子模塊電容器電壓與電容器電容、負載功率因數、調製比及閥側交流電流峰值之間的關繫,併解析齣上下管開關器件的平均電流與有效電流。利用開關器件製造廠商提供的損耗相關參數,對廈門柔性直流示範工程 MMC 在整流狀態和逆變狀態下的損耗和結溫進行計算。計算結果錶明,損耗計算和結溫估算模型能為 MMC 冷卻繫統的配置提供參攷。
대모괴화다전평환류기(MMC)재정현맥관조제방식하자모괴상하관개관기건적투입개솔진행분석。결합상하관개관기건적투입개솔,도출상하관개관기건등효전류적표체식。이자모괴전용기재일개기빈주기내적전압변화량시령위기출,추도출자모괴전용기전압여전용기전용、부재공솔인수、조제비급벌측교류전류봉치지간적관계,병해석출상하관개관기건적평균전류여유효전류。이용개관기건제조엄상제공적손모상관삼수,대하문유성직류시범공정 MMC 재정류상태화역변상태하적손모화결온진행계산。계산결과표명,손모계산화결온고산모형능위 MMC 냉각계통적배치제공삼고。
The active probability of upper and lower controllable switches of a modular multilevel converter(MMC)is analyzed under sinusoidal pulse width modulation.By referring to the active probability,the equivalent current of the upper or lower controllable switch can be derived.Then,based on voltage variation of the submodule capacitor in each fundamental period being zero,the voltage of the submodule capacitor can be obtained according to the capacitance of the capacitor,power factor, modulation ratio,AC current peak on valve side,and so on.And based on the equivalent current of the upper or lower controllable switch,the average current and effective current can be derived,respectively.Using the related parameters of the power losses of the controllable switch provided by the manufacturer,the power losses and j unction temperatures of the controllable switch of Xiamen voltage source converter based high voltage direct current(VSC-HVDC)demonstration project are calculated under rectification operation and inverter operation conditions of the MMC,respectively.The results of the loss evaluation model and j unction temperature evaluation model show that the evaluation models are able to provide the MMC cooling system configuration with reference.