内桥接线是110 kV 变电站广泛采用的电气主接线方式,介绍了一起内桥接线的110 kV 变电站主变压器低压侧故障相关保护的动作过程。该故障为主变压器低压侧断路器因触指长期过热失去弹性,触头脱落造成相间短路,因主变压器高后备保护拒动,上级220 kV 变电站线路保护动作并重合,备自投不合理动作,备用线路投入,故障点多次冲击,造成低压断路器烧毁,全站失电。此故障具有一定的典型性,说明典型设计中保护配置存在一定问题。文中对这起故障的保护动作行为进行了全面分析,对如何合理配置保护,避免相同类型故障的发生,提出了建议与对策,对内桥接线变电站的保护配置与整定、运行与维护有参考意义。
內橋接線是110 kV 變電站廣汎採用的電氣主接線方式,介紹瞭一起內橋接線的110 kV 變電站主變壓器低壓側故障相關保護的動作過程。該故障為主變壓器低壓側斷路器因觸指長期過熱失去彈性,觸頭脫落造成相間短路,因主變壓器高後備保護拒動,上級220 kV 變電站線路保護動作併重閤,備自投不閤理動作,備用線路投入,故障點多次遲擊,造成低壓斷路器燒燬,全站失電。此故障具有一定的典型性,說明典型設計中保護配置存在一定問題。文中對這起故障的保護動作行為進行瞭全麵分析,對如何閤理配置保護,避免相同類型故障的髮生,提齣瞭建議與對策,對內橋接線變電站的保護配置與整定、運行與維護有參攷意義。
내교접선시110 kV 변전참엄범채용적전기주접선방식,개소료일기내교접선적110 kV 변전참주변압기저압측고장상관보호적동작과정。해고장위주변압기저압측단로기인촉지장기과열실거탄성,촉두탈락조성상간단로,인주변압기고후비보호거동,상급220 kV 변전참선로보호동작병중합,비자투불합리동작,비용선로투입,고장점다차충격,조성저압단로기소훼,전참실전。차고장구유일정적전형성,설명전형설계중보호배치존재일정문제。문중대저기고장적보호동작행위진행료전면분석,대여하합리배치보호,피면상동류형고장적발생,제출료건의여대책,대내교접선변전참적보호배치여정정、운행여유호유삼고의의。
Inner-bridge configuration is a kind of main electrical connection widely used in 1 10 kV substations.This paper describes the protection action process during a circuit breaker fault on the low voltage side of the main transformer in a 1 10 kV substation with inner-bridge configuration.The long-term overheat made the button contact of the low voltage side circuit breaker of the transformer lose its elasticity.The contact fall off caused an interphase short circuit.Since the high voltage side back-up protection of the transformer failed to operate,the line protection and recloser of the superior 220 kV substation acted. And automatic switchover acted irrationally while the backup line put in.The circuit breaker was damaged by the rush more than once until the substation lost power.The fault is to a certain extent typical of a power system with problems in the design of its protection configuration.An overall analysis is made by the authors on the protection action process of the fault alongside suggestions and countermeasures for optimizing main protection configuration and setting,as well as operation and maintenance of inner-bridge configuration.