针对寒冷地区周边无热网且环境要求较高的建筑对象,提出了利用低谷电驱动的空气源双级耦合热泵蓄能空调系统,介绍了系统的组成和运行原理,分析确定了系统优化目标变量,建立了系统优化数学模型,针对126m2某办公建筑,研究了热泵容量和关闭温度对经济性的影响规律,结果表明:在乌鲁木齐的气候条件下,热泵的最优关闭温度为-20℃,额定制热量为8kW,系统全年平均 COP 为1.71,系统全年运行费用仅较集中供热和分体空调方案高4%,表明该系统具有一定的应用可行性。
針對寒冷地區週邊無熱網且環境要求較高的建築對象,提齣瞭利用低穀電驅動的空氣源雙級耦閤熱泵蓄能空調繫統,介紹瞭繫統的組成和運行原理,分析確定瞭繫統優化目標變量,建立瞭繫統優化數學模型,針對126m2某辦公建築,研究瞭熱泵容量和關閉溫度對經濟性的影響規律,結果錶明:在烏魯木齊的氣候條件下,熱泵的最優關閉溫度為-20℃,額定製熱量為8kW,繫統全年平均 COP 為1.71,繫統全年運行費用僅較集中供熱和分體空調方案高4%,錶明該繫統具有一定的應用可行性。
침대한랭지구주변무열망차배경요구교고적건축대상,제출료이용저곡전구동적공기원쌍급우합열빙축능공조계통,개소료계통적조성화운행원리,분석학정료계통우화목표변량,건립료계통우화수학모형,침대126m2모판공건축,연구료열빙용량화관폐온도대경제성적영향규률,결과표명:재오로목제적기후조건하,열빙적최우관폐온도위-20℃,액정제열량위8kW,계통전년평균 COP 위1.71,계통전년운행비용부교집중공열화분체공조방안고4%,표명해계통구유일정적응용가행성。
Aim at the buildings with no heating network around and high environmental protection requirements in cold areas, the air source double stage coupled heat pump conditioning system with an energy storage tank driven by the lower price electricity was put forward.The system composition and operation principle were introduced,and then the optimization target variable was de-termined by analyzing,the mathematical model was set up for system optimization design.Taking the 126m2 office building as the research object,the impact on the economy about capacity and shutdown temperature of the heat pump was studied.The results show that under the climate condition of Urumqi,the optimal shutdown temperature of coupled heat pump is 20℃,rated heating capacity is 8kW,the annual system average coefficient of performance (COP)is 1.71,and the annual operating cost is 4% higher than the centralized heating and split air conditioning scheme.The above results indicate that the system has certain feasibility.