暖通空调
暖通空調
난통공조
HEATING,VENTILATING & AIR CONDITIONING
2015年
5期
86-92
,共7页
李思成%李昌厚%陈汪海涛
李思成%李昌厚%陳汪海濤
리사성%리창후%진왕해도
热压%室外风压%高层建筑%楼梯间%加压送风系统%网络模拟
熱壓%室外風壓%高層建築%樓梯間%加壓送風繫統%網絡模擬
열압%실외풍압%고층건축%루제간%가압송풍계통%망락모의
stack effect pressure%outdoor wind pressure%high-rise building%stairwell%pressurization supply air system%network simulation
以两幢高度不同的高层建筑为例,利用网络模拟软件 CONTAM3.0模拟分析了热压及室外风压单独作用和二者耦合作用对楼梯间加压送风效果的影响。结果显示:建筑高度、建筑内外温差、室外风的风向和风速都会影响楼梯间加压送风效果;由建筑内外温差产生的热压作用会导致楼梯间压力重新分布,冬季的热压作用极可能导致楼梯间的压力小于安全阈值,使加压送风系统失效;当热压和室外风压耦合作用时,最不利情况是夏季建筑上部迎风面房间着火和冬季建筑下部迎风面房间着火,这两种情况下着火层前室门处的压差均降至6 Pa 左右,远低于规范规定的25 Pa,导致楼梯间加压送风系统失效。
以兩幢高度不同的高層建築為例,利用網絡模擬軟件 CONTAM3.0模擬分析瞭熱壓及室外風壓單獨作用和二者耦閤作用對樓梯間加壓送風效果的影響。結果顯示:建築高度、建築內外溫差、室外風的風嚮和風速都會影響樓梯間加壓送風效果;由建築內外溫差產生的熱壓作用會導緻樓梯間壓力重新分佈,鼕季的熱壓作用極可能導緻樓梯間的壓力小于安全閾值,使加壓送風繫統失效;噹熱壓和室外風壓耦閤作用時,最不利情況是夏季建築上部迎風麵房間著火和鼕季建築下部迎風麵房間著火,這兩種情況下著火層前室門處的壓差均降至6 Pa 左右,遠低于規範規定的25 Pa,導緻樓梯間加壓送風繫統失效。
이량당고도불동적고층건축위례,이용망락모의연건 CONTAM3.0모의분석료열압급실외풍압단독작용화이자우합작용대루제간가압송풍효과적영향。결과현시:건축고도、건축내외온차、실외풍적풍향화풍속도회영향루제간가압송풍효과;유건축내외온차산생적열압작용회도치루제간압력중신분포,동계적열압작용겁가능도치루제간적압력소우안전역치,사가압송풍계통실효;당열압화실외풍압우합작용시,최불리정황시하계건축상부영풍면방간착화화동계건축하부영풍면방간착화,저량충정황하착화층전실문처적압차균강지6 Pa 좌우,원저우규범규정적25 Pa,도치루제간가압송풍계통실효。
Taking two high-rise buildings as examples,simulates the influence of the stack effect and the wind pressure on the stairwell pressurization supply air system separately and simultaneously with the network simulation software CONTAM3.0.The result shows that the building height,the temperature difference between inside and outside of the building,the direction and magnitude of outdoor wind velocity will all have an effect on the stairwell pressurization supply air system.The stack effect caused by the temperature difference between inside and outside of the building will result in redistribution of pressure in the stairwell,and the stack effect is very likely to cause the pressure in the stairwell smaller than the safety threshold,which may cause the stairwell pressurization supply air system fail.With the coupling of the stack effect and the outdoor wind pressure,the most unfavorable situations occur when the windward fire room is on upper floor in summer or on lower floor in winter,in which the pressure difference between lobby and corridor is down to about 6 Pa,which is much less than 25 Pa stipulated in the standards,and that may cause the malfunction of stairwell pressurization supply air system.