暖通空调
暖通空調
난통공조
HEATING,VENTILATING & AIR CONDITIONING
2015年
5期
12-16
,共5页
太阳能供暖系统%太阳能贡献率%辅助热源%一次能耗%节能
太暘能供暖繫統%太暘能貢獻率%輔助熱源%一次能耗%節能
태양능공난계통%태양능공헌솔%보조열원%일차능모%절능
solar heating system%solar fraction%auxiliary heat source%primary energy consumption%energy efficiency
根据太阳能贡献率和辅助加热设备的能源效率,将系统的能耗折算成一次能源,分析不同辅助热源对太阳能供暖系统节能性的影响,认为主动式太阳能供暖系统要达到节能效果必须满足一定的前提条件。研究结果表明:辅助热源方式和太阳能贡献率对系统的节能性影响很大;相对于燃气锅炉单独供暖,电加热辅助太阳能供暖系统只有在太阳能贡献率高于65.4%时才节能,而大多数系统的太阳能贡献率很难达到这么高,因此要尽量避免使用;热泵辅助太阳能供暖系统在大多数情况下都是节能的(热泵的平均 COP =2.5时,太阳能贡献率需高于7%);采用平均COP 高于3.0的热泵或采用燃气锅炉作为辅助热源时,系统都是节能的,太阳能贡献率越高,节能效果越明显。
根據太暘能貢獻率和輔助加熱設備的能源效率,將繫統的能耗摺算成一次能源,分析不同輔助熱源對太暘能供暖繫統節能性的影響,認為主動式太暘能供暖繫統要達到節能效果必鬚滿足一定的前提條件。研究結果錶明:輔助熱源方式和太暘能貢獻率對繫統的節能性影響很大;相對于燃氣鍋爐單獨供暖,電加熱輔助太暘能供暖繫統隻有在太暘能貢獻率高于65.4%時纔節能,而大多數繫統的太暘能貢獻率很難達到這麽高,因此要儘量避免使用;熱泵輔助太暘能供暖繫統在大多數情況下都是節能的(熱泵的平均 COP =2.5時,太暘能貢獻率需高于7%);採用平均COP 高于3.0的熱泵或採用燃氣鍋爐作為輔助熱源時,繫統都是節能的,太暘能貢獻率越高,節能效果越明顯。
근거태양능공헌솔화보조가열설비적능원효솔,장계통적능모절산성일차능원,분석불동보조열원대태양능공난계통절능성적영향,인위주동식태양능공난계통요체도절능효과필수만족일정적전제조건。연구결과표명:보조열원방식화태양능공헌솔대계통적절능성영향흔대;상대우연기과로단독공난,전가열보조태양능공난계통지유재태양능공헌솔고우65.4%시재절능,이대다수계통적태양능공헌솔흔난체도저요고,인차요진량피면사용;열빙보조태양능공난계통재대다수정황하도시절능적(열빙적평균 COP =2.5시,태양능공헌솔수고우7%);채용평균COP 고우3.0적열빙혹채용연기과로작위보조열원시,계통도시절능적,태양능공헌솔월고,절능효과월명현。
According to the solar fraction and the energy efficiency of auxiliary heating equipments, analyses the effects of different auxiliary heat sources on the energy efficiency of active solar heating systems by converting energy consumption to primary energy,and believes that the active solar heating system must satisfy certain conditions for achieving energy saving effect.The results indicate that the auxiliary heat source and the solar fraction have a great impact on the energy efficiency of solar heating systems.Compared to the gas-fired boiler heating alone,the solar heating system assisted by electric heating is energy efficient only when the solar fraction is greater than 65.4%,which is very difficult to achieve for many real systems.The primary energy consumption of the solar heating system assisted by heat pump is lower in general instances (when the average COP of heat pump is 2.5,the solar fraction should be greater than 7%).When heat pumps with average COP above 3.0 or gas-fired boilers are used as auxiliary heat sources,the solar heating system is energy efficient,and the higher the solar fraction is,the more obvious the energy saving effect is.