水电站%GIL%对地放电
水電站%GIL%對地放電
수전참%GIL%대지방전
hydropower station%Gas Insulated Transmission Line ( GIL)%discharge
某水电站C相管道母线( GIL)在正常运行中,突然发生导体对外壳放电故障,导致该条线路停运。依据故障前的监测数据和故障后的气体分解产物分析了故障的原因,就隧道管母线监测手段不完善的问题提出了改进建议,更换该段管道母线后故障消除。
某水電站C相管道母線( GIL)在正常運行中,突然髮生導體對外殼放電故障,導緻該條線路停運。依據故障前的鑑測數據和故障後的氣體分解產物分析瞭故障的原因,就隧道管母線鑑測手段不完善的問題提齣瞭改進建議,更換該段管道母線後故障消除。
모수전참C상관도모선( GIL)재정상운행중,돌연발생도체대외각방전고장,도치해조선로정운。의거고장전적감측수거화고장후적기체분해산물분석료고장적원인,취수도관모선감측수단불완선적문제제출료개진건의,경환해단관도모선후고장소제。
A sudden shut-down accident of the C-phase GIL tubular busbar in a hydropower station during its normal op-eration was encountered due to a discharge fault of the conductor to the case.Possible reasons of this fault are analyzed with the monitoring data before the accident and the breakdown products of the insulation gas after the accident.Im-provement measures are suggested for the monitoring of the tubular busbar.After the replacement of the faulty busbar, the accident is solved.