电压互感器(TV)%误动事例%二次回路%多点接地
電壓互感器(TV)%誤動事例%二次迴路%多點接地
전압호감기(TV)%오동사례%이차회로%다점접지
TV%malfunction instance%secondary circuit multi-point grounding
电压互感器(TV)二次回路多点接地易对继电保护的动作行为产生严重干扰。分析了一起TV两点接地导致线路保护误动事例,并提出一种检查运行变电站TV二次回路接地点的试验方法,可以有效消除变电站的TV二次回路多点接地隐患,确保电网的安全运行。
電壓互感器(TV)二次迴路多點接地易對繼電保護的動作行為產生嚴重榦擾。分析瞭一起TV兩點接地導緻線路保護誤動事例,併提齣一種檢查運行變電站TV二次迴路接地點的試驗方法,可以有效消除變電站的TV二次迴路多點接地隱患,確保電網的安全運行。
전압호감기(TV)이차회로다점접지역대계전보호적동작행위산생엄중간우。분석료일기TV량점접지도치선로보호오동사례,병제출일충검사운행변전참TV이차회로접지점적시험방법,가이유효소제변전참적TV이차회로다점접지은환,학보전망적안전운행。
The multi-point grounding of the TV secondary circuit is easy to seriously disrupt the line protection action.An instances of the line protection malfunction caused by two-point grounding with TV is analyzed.An experimental method of examining the TV secondary circuit grounding point in operation substation is proposed through this case,which can effectively eliminate the TV secondary circuit substation multi-point grounding risks and ensure the safe operation of power grid.