地源热泵%控制策略%数值模拟%热平衡
地源熱泵%控製策略%數值模擬%熱平衡
지원열빙%공제책략%수치모의%열평형
ground source heatpum p%controlstrategy%num ericalsim ulation%heatbalance
以南京某复合式地源热泵系统为研究对象,通过能耗模拟软件E nergyplus分析其天棚辐射空调系统的能耗,计算出地埋管侧全年累计散热量与取热量之比为3.97:1。该项目采用复合式的地源热泵系统,本文分析辅助散热设备运行控制策略以保证地源热泵系统可持续高效运行。比较三种控制策略得出:温差控制不适合散热量与取热量严重失衡的系统,因其控制温差不易确定,辅助散热设备启停频繁,且难以保证系统多年运行地下热平衡;热泵进口水温控制是保证地下热平衡的有效措施,但是需要选择合理的控制参数值,辅助散热设备启动较频繁;定时开启控制不仅能够保证系统持续高效运行,而且控制策略易于实施。
以南京某複閤式地源熱泵繫統為研究對象,通過能耗模擬軟件E nergyplus分析其天棚輻射空調繫統的能耗,計算齣地埋管側全年纍計散熱量與取熱量之比為3.97:1。該項目採用複閤式的地源熱泵繫統,本文分析輔助散熱設備運行控製策略以保證地源熱泵繫統可持續高效運行。比較三種控製策略得齣:溫差控製不適閤散熱量與取熱量嚴重失衡的繫統,因其控製溫差不易確定,輔助散熱設備啟停頻繁,且難以保證繫統多年運行地下熱平衡;熱泵進口水溫控製是保證地下熱平衡的有效措施,但是需要選擇閤理的控製參數值,輔助散熱設備啟動較頻繁;定時開啟控製不僅能夠保證繫統持續高效運行,而且控製策略易于實施。
이남경모복합식지원열빙계통위연구대상,통과능모모의연건E nergyplus분석기천붕복사공조계통적능모,계산출지매관측전년루계산열량여취열량지비위3.97:1。해항목채용복합식적지원열빙계통,본문분석보조산열설비운행공제책략이보증지원열빙계통가지속고효운행。비교삼충공제책략득출:온차공제불괄합산열량여취열량엄중실형적계통,인기공제온차불역학정,보조산열설비계정빈번,차난이보증계통다년운행지하열평형;열빙진구수온공제시보증지하열평형적유효조시,단시수요선택합리적공제삼수치,보조산열설비계동교빈번;정시개계공제불부능구보증계통지속고효운행,이차공제책략역우실시。
A Hybrid Ground Source HeatPum p system (HGSHPs)in Nanjing isresearched.The all-energy analysis sim ulation softw are E nergyplus is used to analyze ceiling radiation air conditioning system energy perform ance. B y analyzing the energy sim ulation results, the ratio of the heat dissipation and absorption to the ground by the ground source heatexchanger is 3.97:1 in one year.So auxiliary cooling equipm entis used and this paper tries to find the right control strategy and param eters to ensure system sustainable and operated w ith high efficiency. T hree control strategies forHGSHPssustainable operation are com pared.The resultsshow that:controlled by tem perature difference doesnot suitfor heatbalance control,for the tem perature difference is difficultto determ ine,and the auxiliary cooling equipm ent starts and stops frequently;controlled by the heat pum p inlet w ater tem perature insure the heat balance, but reasonable controlparam eters is im portant;controlled by open tim ing can notonly m ake sure the heatbalance,itcan m ake sure the H G SH Ps operated w ith high efficiency.