中国电机工程学报
中國電機工程學報
중국전궤공정학보
Proceedings of the CSEE
2015年
11期
2718-2725,后插10
,共9页
孙全才%程浩忠%张健%王琦%宋越%刘明松%杨堤%李诗旸
孫全纔%程浩忠%張健%王琦%宋越%劉明鬆%楊隄%李詩旸
손전재%정호충%장건%왕기%송월%류명송%양제%리시양
暂态电压安全%动态无功备用%原对偶内点法%轨迹灵敏度
暫態電壓安全%動態無功備用%原對偶內點法%軌跡靈敏度
잠태전압안전%동태무공비용%원대우내점법%궤적령민도
transient voltage security%dynamic reactive power reserve%primal dual interior point method%trace sensitivity
电力系统动态无功储备对提高系统暂态电压安全水平具有重要作用,因此提出一种在系统暂态过程中考虑暂态电压安全的无功备用概念,并给出其对暂态电压安全贡献的评价方法及相应的修正系数.通过轨迹灵敏度方法实现对修正后的无功源动态无功备用的计算,建立提高系统暂态电压安全水平的无功备用优化模型,利用原对偶内点法进行求解.IEEE 39节点算例结果表明,所提3种权重系数合理、有效,通过该评价方式可以充分考虑到无功备用点对点的支撑能力以及故障严重性对无功备用的要求程度,通过系统动态无功备用的优化可提高系统的整体暂态电压安全水平,因此所提方法能够有效地预防系统故障时暂态电压安全问题的发生.
電力繫統動態無功儲備對提高繫統暫態電壓安全水平具有重要作用,因此提齣一種在繫統暫態過程中攷慮暫態電壓安全的無功備用概唸,併給齣其對暫態電壓安全貢獻的評價方法及相應的脩正繫數.通過軌跡靈敏度方法實現對脩正後的無功源動態無功備用的計算,建立提高繫統暫態電壓安全水平的無功備用優化模型,利用原對偶內點法進行求解.IEEE 39節點算例結果錶明,所提3種權重繫數閤理、有效,通過該評價方式可以充分攷慮到無功備用點對點的支撐能力以及故障嚴重性對無功備用的要求程度,通過繫統動態無功備用的優化可提高繫統的整體暫態電壓安全水平,因此所提方法能夠有效地預防繫統故障時暫態電壓安全問題的髮生.
전력계통동태무공저비대제고계통잠태전압안전수평구유중요작용,인차제출일충재계통잠태과정중고필잠태전압안전적무공비용개념,병급출기대잠태전압안전공헌적평개방법급상응적수정계수.통과궤적령민도방법실현대수정후적무공원동태무공비용적계산,건립제고계통잠태전압안전수평적무공비용우화모형,이용원대우내점법진행구해.IEEE 39절점산례결과표명,소제3충권중계수합리、유효,통과해평개방식가이충분고필도무공비용점대점적지탱능력이급고장엄중성대무공비용적요구정도,통과계통동태무공비용적우화가제고계통적정체잠태전압안전수평,인차소제방법능구유효지예방계통고장시잠태전압안전문제적발생.
Dynamic reactive power reserve of power system is vital to improve transient voltage security. An novel definition of reactive power reserve considering transient voltage security in transient procession was proposed. Correction coefficient to evaluate reactive power reserve's contribution to transient voltage security was given. Corrected reactive power reserve was computed through trace sensitivity method. Then an optimization model to enhance transient voltage security was built. It was solved by primal dual interior point method. Testing on IEEE 39-node system,it is indicated that three weight coefficients proposed are reasonable and effective. The evaluation method can give consideration both supporting capacity of one bus to the other and demand of reactive power reserve according to severity of faults. The system's transient voltage security is enhanced by the way of optimization of system's dynamic reactive power reserve. Hence, the method proposed can be used to prevent the happening of transient voltage collapse during system's fault.