2015年
10期
12-16,65
,共6页
王建成%张涛%张建成%刘崇都%王欣%吴军轶
王建成%張濤%張建成%劉崇都%王訢%吳軍軼
왕건성%장도%장건성%류숭도%왕흔%오군질
电流互感器%差动保护%越级误动%额定二次极限电动势%保护二次等效电动势%暂态系数%比例制动特性
電流互感器%差動保護%越級誤動%額定二次極限電動勢%保護二次等效電動勢%暫態繫數%比例製動特性
전류호감기%차동보호%월급오동%액정이차겁한전동세%보호이차등효전동세%잠태계수%비례제동특성
TA%differential protection%over-reach maloperation%rated secondary limiting electromotive force%protection secondary electromotive force%transient factor%ratio brake characteristic
差动保护“抗饱和”软件抓住1/5周波内TA(电流互感器)线性传变完成程序鉴别,这对采用高漏磁TPY级TA的主变差动保护防误动无疑上了一道“双保险”。但500 kV重合闸扰动下的无剩磁限制5P25级TA很难提供出大于1/5周波的线性传变,极易造成500 kV主变差动保护鉴别区内外故障出错而引发误动。分析了秦山核电厂4台主变差动保护所用20个5P级TA存在的问题,依据相关规范进行计算校核,优化调整TA特征参数,拓宽瞬态下TA线性传变时限,满足“抗饱和”软件鉴别区内外故障的判别条件。
差動保護“抗飽和”軟件抓住1/5週波內TA(電流互感器)線性傳變完成程序鑒彆,這對採用高漏磁TPY級TA的主變差動保護防誤動無疑上瞭一道“雙保險”。但500 kV重閤閘擾動下的無剩磁限製5P25級TA很難提供齣大于1/5週波的線性傳變,極易造成500 kV主變差動保護鑒彆區內外故障齣錯而引髮誤動。分析瞭秦山覈電廠4檯主變差動保護所用20箇5P級TA存在的問題,依據相關規範進行計算校覈,優化調整TA特徵參數,拓寬瞬態下TA線性傳變時限,滿足“抗飽和”軟件鑒彆區內外故障的判彆條件。
차동보호“항포화”연건조주1/5주파내TA(전류호감기)선성전변완성정서감별,저대채용고루자TPY급TA적주변차동보호방오동무의상료일도“쌍보험”。단500 kV중합갑우동하적무잉자한제5P25급TA흔난제공출대우1/5주파적선성전변,겁역조성500 kV주변차동보호감별구내외고장출착이인발오동。분석료진산핵전엄4태주변차동보호소용20개5P급TA존재적문제,의거상관규범진행계산교핵,우화조정TA특정삼수,탁관순태하TA선성전변시한,만족“항포화”연건감별구내외고장적판별조건。
Saturation-resistance software for differential protection caught TA(current transformer) linear trans-fer in one-fifth of the cycle to finish the verification of programme, which undoubtedly gives double insurance to "anti-maloperation" of main transformer differential protection that adopts high flux leakage TA of TPY class. But no-limited-leakage-flux TA with 5P25 class under the distortion of 500 kV auto-closure is difficult to provide linear transfer with its cycle not larger than 1/5, resulting in faults in and out of 500 kV main transformer differential protection region and maloperation. Problems in twenty 5P-class TAs for differential protection of four main transformers in Qinshan Second Nuclear Power Plant are analyzed and characteristic parameters of TA are optimized through calculation and verification in line with relevant regulations; time limit of TA linear transfer in transient state is expanded to meet the judgment requirements that saturation-re-sistance software needs to identify internal and external faults.