石油与天然气化工
石油與天然氣化工
석유여천연기화공
Chemical Engineering of Oil and Gas
2015年
5期
100-104,110
,共6页
关联报警%报警抑制%聚类分析%报警优先级%TE模型
關聯報警%報警抑製%聚類分析%報警優先級%TE模型
관련보경%보경억제%취류분석%보경우선급%TE모형
correlated alarms%alarm suppression%cluster analysis%alarm priority%TE process
针对目前流程工业报警系统中普遍存在的报警系统效率低、连锁报警多的现象,提出一种基于过程数据的关联报警分组和抑制策略。该策略采用离差平方和法对过程数据进行聚类分析,根据距离系数把关联的报警变量分组;并利用报警优先级量化规则,从响应时间和后果严重度两方面计算报警的优先级分值,以此确定报警小组中需要及时响应和抑制的报警。该策略有助于控制员理解报警间的关联关系、提高对连锁报警的响应效率。最后在TE模型中运行测试,验证了该策略的有效性和实用性。
針對目前流程工業報警繫統中普遍存在的報警繫統效率低、連鎖報警多的現象,提齣一種基于過程數據的關聯報警分組和抑製策略。該策略採用離差平方和法對過程數據進行聚類分析,根據距離繫數把關聯的報警變量分組;併利用報警優先級量化規則,從響應時間和後果嚴重度兩方麵計算報警的優先級分值,以此確定報警小組中需要及時響應和抑製的報警。該策略有助于控製員理解報警間的關聯關繫、提高對連鎖報警的響應效率。最後在TE模型中運行測試,驗證瞭該策略的有效性和實用性。
침대목전류정공업보경계통중보편존재적보경계통효솔저、련쇄보경다적현상,제출일충기우과정수거적관련보경분조화억제책략。해책략채용리차평방화법대과정수거진행취류분석,근거거리계수파관련적보경변량분조;병이용보경우선급양화규칙,종향응시간화후과엄중도량방면계산보경적우선급분치,이차학정보경소조중수요급시향응화억제적보경。해책략유조우공제원리해보경간적관련관계、제고대련쇄보경적향응효솔。최후재TE모형중운행측시,험증료해책략적유효성화실용성。
To solve the common problems of the alarm system in the process industry ,such as low efficiency and frequent interlocking alarm ,this paper proposes a grouping and suppression strategy for correlated alarms based on process data .The Ward Method was used in this strategy for cluster analy‐sis of the process data ,and distance coefficient was the consideration to group the alarm variables that may related .Quantization regulations of alarm priority were introduced to identify the alarms needing response or suppression in an alarm group via analyzing the accurate priority score from both response time and severity of consequences .It is helpful for controllers to recognize the correlation among a‐larms ,and improve the response efficiency .The strategy yields an effective alarm management that can help plant owners and operators to comply with the standards for alarm management such as AN‐SI/ISA 18 .2 (2009) and EEMUA 191 (2007) which set limits on the number of alarms per unit time for an operator .The effectiveness of the approach is illustrated by successful application in TE process model w here a significant reduction of alarms has been achieved .