山西电力
山西電力
산서전력
Shanxi Electric Power
2015年
5期
6-8
,共3页
油中溶解气体%550kV变压器%快速增长%裸金属放电
油中溶解氣體%550kV變壓器%快速增長%裸金屬放電
유중용해기체%550kV변압기%쾌속증장%라금속방전
dissolved gas in oil%550 kV transformer%rapid increasing%bare metal discharge
通过油中溶解气体跟踪分析发现某550 kV变压器乙炔含量突然快速增长.结合历史运行工况及测试数据综合分析,判定其内部存在低能量裸金属放电,故障未涉及固体绝缘.将主变返厂吊罩,查明变压器运行异常主要由高压引线装置支撑衬条缺失引起,并提出了相应处理措施,保障了变压器的安全可靠运行.
通過油中溶解氣體跟蹤分析髮現某550 kV變壓器乙炔含量突然快速增長.結閤歷史運行工況及測試數據綜閤分析,判定其內部存在低能量裸金屬放電,故障未涉及固體絕緣.將主變返廠弔罩,查明變壓器運行異常主要由高壓引線裝置支撐襯條缺失引起,併提齣瞭相應處理措施,保障瞭變壓器的安全可靠運行.
통과유중용해기체근종분석발현모550 kV변압기을결함량돌연쾌속증장.결합역사운행공황급측시수거종합분석,판정기내부존재저능량라금속방전,고장미섭급고체절연.장주변반엄조조,사명변압기운행이상주요유고압인선장치지탱츤조결실인기,병제출료상응처리조시,보장료변압기적안전가고운행.
Acetylene content rapid increasing is revealed by testing the dissolved gas-in-oil of a 550 kV transformer. The causes of this fault are discussed based on historical operating conditions and testing data. It is pointed out that there is low energy bare metal discharge in transformer,but it has not affected solid insulation. The transformer's abnormal operation is mainly caused by the lack of high-voltage wire device support strips,and corresponding treatment measures are proposed to ensure security and reliable operation of the transformer.