中国电机工程学报
中國電機工程學報
중국전궤공정학보
Proceedings of the CSEE
2015年
22期
5768-5777
,共10页
张放%程林%黎雄%曾敏%孙元章%宋云亭
張放%程林%黎雄%曾敏%孫元章%宋雲亭
장방%정림%려웅%증민%손원장%송운정
广域测量系统%闭环控制%时延%线性估计模型
廣域測量繫統%閉環控製%時延%線性估計模型
엄역측량계통%폐배공제%시연%선성고계모형
wide-area measurement system (WAMS)%closed-loop control%delay%latency%affine evaluation model
由2篇论文组成的系列文章旨在研究广域闭环控制系统(wide-area closed-loop control system,WACS)中时延的测量方法及其特性建模。该文作为系列文章的第1篇,研究WACS中的时延产生,将WACS时延归为通信时延和操作时延两大类并分别研究。针对通信时延,提出一种线性估计模型,继而实测并分析贵州电网广域测量系统的通信时延,验证该线性估计模型的正确性。针对操作时延,分析实验室条件下WACS 设备的操作时延,提出基于RTDS 硬件在环平台的波形对比测量法,并用此方法实测WACS 硬件在环系统中的操作时延。分析结果表明,实验室条件下操作时延可以用正态分布拟合其分布特性。该文对时延的分析及测试结果是研究WACS 闭环时延的重要基础。
由2篇論文組成的繫列文章旨在研究廣域閉環控製繫統(wide-area closed-loop control system,WACS)中時延的測量方法及其特性建模。該文作為繫列文章的第1篇,研究WACS中的時延產生,將WACS時延歸為通信時延和操作時延兩大類併分彆研究。針對通信時延,提齣一種線性估計模型,繼而實測併分析貴州電網廣域測量繫統的通信時延,驗證該線性估計模型的正確性。針對操作時延,分析實驗室條件下WACS 設備的操作時延,提齣基于RTDS 硬件在環平檯的波形對比測量法,併用此方法實測WACS 硬件在環繫統中的操作時延。分析結果錶明,實驗室條件下操作時延可以用正態分佈擬閤其分佈特性。該文對時延的分析及測試結果是研究WACS 閉環時延的重要基礎。
유2편논문조성적계렬문장지재연구엄역폐배공제계통(wide-area closed-loop control system,WACS)중시연적측량방법급기특성건모。해문작위계렬문장적제1편,연구WACS중적시연산생,장WACS시연귀위통신시연화조작시연량대류병분별연구。침대통신시연,제출일충선성고계모형,계이실측병분석귀주전망엄역측량계통적통신시연,험증해선성고계모형적정학성。침대조작시연,분석실험실조건하WACS 설비적조작시연,제출기우RTDS 경건재배평태적파형대비측량법,병용차방법실측WACS 경건재배계통중적조작시연。분석결과표명,실험실조건하조작시연가이용정태분포의합기분포특성。해문대시연적분석급측시결과시연구WACS 폐배시연적중요기출。
This two-part paper aims to study the characteristics and characterization for the delays in a wide-area closed-loop control system (WACS). In the first part, the delays were studied basing on the structure and information flow of the WACS, and they were divided into the communication delays and the operational delays. For the communication delay, an affine evaluation model was presented. The communication delays of the WAMS in Guizhou Power Grid was also measured and analyzed, and the affine evaluation model was verified by these results. For the operational delay, a real-time digital simulator (RTDS) hardware-in-the-loop measurement method was proposed, and the operational delays were measured and analyzed using this method. The results indicate that, a normal distribution fits for the characterization of the operational delay in laboratory. The measured results and analysis presented in this paper are important for the research on the closed-loop delays of WACS.