中国电机工程学报
中國電機工程學報
중국전궤공정학보
Proceedings of the CSEE
2015年
23期
6235-6245
,共11页
胡榕%崔翔%陈维江%张卫东%李志兵%戴敏
鬍榕%崔翔%陳維江%張衛東%李誌兵%戴敏
호용%최상%진유강%장위동%리지병%대민
特高压%气体绝缘开关设备%瞬态外壳电压%测量装置%性能测试%建模仿真
特高壓%氣體絕緣開關設備%瞬態外殼電壓%測量裝置%性能測試%建模倣真
특고압%기체절연개관설비%순태외각전압%측량장치%성능측시%건모방진
ultra high voltage (UHV)%gas insulated switchgear (GIS)%transient enclosure voltage (TEV)%measuring device%performance test%modeling and simulation
特高压(ultra high voltage,UHV)气体绝缘开关设备(gas insulated switchgear,GIS)的瞬态外壳电压(transient enclosure voltage,TEV)具有陡波前、高幅值和宽频带等特点,可能危害到接触GIS设备的运行人员安全及GIS设备监控系统的正常运行。为此,准确测量TEV是十分必要的。该文采用电阻性阻抗分压法测量TEV,提出TEV典型波形特征和测量要求;依据测量基本要求,研制了抗强电磁干扰的TEV测量装置,并对装置进行一系列的性能试验及电磁兼容与绝缘耐压试验;建立了测量装置和测量/接地屏蔽电缆的等效电路模型,通过仿真计算和试验测试规定了这两种屏蔽电缆的长度上限;最后将测量装置应用于现场 UHV GIS设备的TEV多测点全过程同步测量,结果表明TEV测量装置满足UHV的GIS设备的TEV现场测量。因此,采用文中的TEV测量装置能够获得GIS外壳不同位置的TEV波形特征及分布规律,为TEV的仿真建模提供试验数据。
特高壓(ultra high voltage,UHV)氣體絕緣開關設備(gas insulated switchgear,GIS)的瞬態外殼電壓(transient enclosure voltage,TEV)具有陡波前、高幅值和寬頻帶等特點,可能危害到接觸GIS設備的運行人員安全及GIS設備鑑控繫統的正常運行。為此,準確測量TEV是十分必要的。該文採用電阻性阻抗分壓法測量TEV,提齣TEV典型波形特徵和測量要求;依據測量基本要求,研製瞭抗彊電磁榦擾的TEV測量裝置,併對裝置進行一繫列的性能試驗及電磁兼容與絕緣耐壓試驗;建立瞭測量裝置和測量/接地屏蔽電纜的等效電路模型,通過倣真計算和試驗測試規定瞭這兩種屏蔽電纜的長度上限;最後將測量裝置應用于現場 UHV GIS設備的TEV多測點全過程同步測量,結果錶明TEV測量裝置滿足UHV的GIS設備的TEV現場測量。因此,採用文中的TEV測量裝置能夠穫得GIS外殼不同位置的TEV波形特徵及分佈規律,為TEV的倣真建模提供試驗數據。
특고압(ultra high voltage,UHV)기체절연개관설비(gas insulated switchgear,GIS)적순태외각전압(transient enclosure voltage,TEV)구유두파전、고폭치화관빈대등특점,가능위해도접촉GIS설비적운행인원안전급GIS설비감공계통적정상운행。위차,준학측량TEV시십분필요적。해문채용전조성조항분압법측량TEV,제출TEV전형파형특정화측량요구;의거측량기본요구,연제료항강전자간우적TEV측량장치,병대장치진행일계렬적성능시험급전자겸용여절연내압시험;건립료측량장치화측량/접지병폐전람적등효전로모형,통과방진계산화시험측시규정료저량충병폐전람적장도상한;최후장측량장치응용우현장 UHV GIS설비적TEV다측점전과정동보측량,결과표명TEV측량장치만족UHV적GIS설비적TEV현장측량。인차,채용문중적TEV측량장치능구획득GIS외각불동위치적TEV파형특정급분포규률,위TEV적방진건모제공시험수거。
Transient enclosure voltage (TEV) in ultra high voltage (UHV) gas insulated switchgear (GIS) has steep rise time of waveform, high amplitude, wide frequency band and other characteristics, these may affect the safety of operating personnel touched with GIS and normal operation of GIS monitoring devices. For these reasons, it is necessary to accurately measure TEV. A method of resistive impedance divider was used to measure TEV, typical waveform characteristics of TEV and basic requirements of TEV measuring were proposed; Based on basic requirements of measuring, TEV measuring device of strong anti- electromagnetic interference was developed, a series of performance tests and electromagnetic compatibility and insulation tests were carried out on the device; Equivalent circuits of measuring device and measuring/grounding shielded cables were established, through simulation and experimental test, these maximum lengths of both shielded cables were respectively defined; Finally, the measuring device was applied to TEV multiple measuring points of a whole process simultaneous measurement in UHV GIS on site, these results show that TEV measuring device met TEV measuring on UHV GIS site. Therefore, TEV waveform characteristics and distribution of different locations on GIS enclosure can be obtained by TEV measuring device, these experimental data are provided for TEV modeling and simulation.